Lennox LF25-045A-2, Compact Horizontal Gas Unit Heater, 45000 Btuh, Aluminized Steel Heat Exchanger, 1 Fan, 115VAC
Cat # : 20N06
Model/Part # : LF25-045A-2
Quantity:
Product Overview
Lennox LF25-030-105 Low Profile Compact Gas Unit Heaters
Cabinet:
- Constructed of pre-painted heavy gauge cold rolled steel
- Hinged, reversible door for easy access
- Adjustable louvers are furnished on cabinet for control of air flow direction
- Wiring junction box is conveniently located outside unit cabinet for easy field wiring connections
- Hanging brackets for suspending unit are furnished for field installation
- Unit may be rotated 180 degrees (top for bottom) for ease of installation of gas, electrical and flue locations
Tubular Aluminized Steel Heat Exchanger:
- Tubular heat exchanger is constructed of aluminized steel for superior resistance to corrosion and oxidation
- Curving design of heat exchanger allows complete exposure of heating surfaces to supply air stream
- Dimpled tubes with wrinkle bends allow for maximum heat transfer
- Compact design reduces space requirements in unit cabinet. Heat exchanger has been laboratory life cycle tested
Inshot Burner Assembly:
- Aluminized steel inshot burners provide efficient trouble free operation
- Burner venturi mixes air and gas in correct proportion for proper combustion
- Burner assembly is removable from the unit as a single component for ease of service
Gas Control Valve:
- 24 volt redundant combination gas control valve combines manual shut off switch (On-Off), automatic electric valve (dual) and gas pressure regulation into a compact combination control
Combustion Air Inducer:
- Prepurges heat exchanger and safely vents combustion products
- Operates only during heating cycle
- Blower motor has ball bearings and is thermally protected
Pressure Switch:
- Pressure switch prevents unit operation in case of blocked flue outlet
Limit Control(s):
- Factory installed and accurately located
- Limit control has fixed temperature setting and protects heating system from abnormal operating conditions
Flame Rollout Switch:
- Automatic reset switch is factory installed on the top of the burner box
Controls:
- Combination Direct Spark Ignition/Fan Timer Control Ignition Control
- Electronic direct spark ignition control provides positive and safe main burner ignition.
- Spark is intermittent and occurs only when required.
- Separate electronic flame sensor control assures safe and reliable operation.
- Should loss of flame occur, flame sensor controls will initiate 5 attempts at re-ignition before locking out unit operation.
- Control board contains all necessary controls and relays to operate unit.
- Includes: Fan timer control - fan on 30 seconds (fixed), fan off 150 seconds (fixed), terminal strip for thermostat connections, diagnostic LED for troubleshooting.
- Direct plug-in wiring harness.
- 120V/24V transformer furnished as standard